The Evaluation of the Egress Performance in the Buildings Installed with Luminous Egress Guide-lines

Yong-Hwan Park, Beom-Gyu Kim, Lim Chae-Hyun

· Journal of Korean Institute of Fire Science and Engineering

See on the map

Abstract

Recently luminous egress guide-lines are introduced for the fire safety of residents in the multi-use buildings such as Gosiwon. Little literature, however, on the quantitative and qualitative estimation for the egress performance of the luminous egress guide-lines can be found. This study carried out experimental investigations to evaluate the egress performance of the existing egress guide-lights and new luminous egress guide-lines. The results showed that both luminous egress guide-lines and egress guide-light satisfied the basic performance of KFI requirements. Under the 7 % smoke transmittance, however, luminous egress guide-lines showed 3 times longer visibility and less evacuation time than egress guide-lights. The evacuation density and smoke transmittance have significant effect on the evacuation time increase without the luminous egress guide-lines, however little effect with the installation.